Technical Requirements Table v2.0

See a list of our category definitions here

DesignLights Consortium® Qualified Products List- Non-Residential Applications —
Submit any or all of the following product Information and Testing Results to DesignLights for qualification
*please make note that it is ONE per submission*
PDF Download

Note: Products may continue to apply under v1.7 Technical Requirements until June 7, 2013.

Application

Minimum Light Output

Zonal Lumen Density

Minimum Luminaire Efficacy

Allowable CCTs
(ANSI C78.377-2008)

Minimum CRI

L70 Lumen Maintenance

Minimum Luminaire Warranty

1) Outdoor Pole/Arm-mounted Area and Roadway Luminaires

1,000 lm

=100%: 0–90º, <10%: 80–90º

70 lm/W

<5700K

65

50,000 hrs

5 years

2) Outdoor Pole/Arm-mounted Decorative Luminaires

1,000 lm

>65%: 0–90º

60 lm/W

<5700K

65

50,000 hrs

5 years

3) Outdoor Wall-mounted Area Luminaires

300 lm

=100%: 0–90º,
<10%: 80–90º

70 lm/W

<5700K

65

50,000 hrs

5 years
4) Bollards 500 lm

<15%: 90-110º

0%: >110º

50 lm/W <5700K 65 50,000 hrs 5 years
5) Parking Garage Luminaires

2,000 lm

>30%: 60–80º,

<25%: 70–80º

75 lm/W

<5700K

65

50,000 hrs

5 years
6) Fuel Pump Canopy 2,000 lm ≥40%: 0- 40° ≥40%: 40- 70° 80 lm/W <5700K 65 50,000 hrs 5 years
7) Landscape/Accent Flood and Spot Lighting 250 lm (<1000 lm) ≥85%: 0-90° 65 lm/w ≤5700K 65 50,000 hrs 5 years
8) Architectural Flood and Spot Lighting 1,000 lm ≥85%: 0-90° 75 lm/w ≤5700K 65 50,000 hrs 5 years
9) Stairwell and Passageway Lighting 750 lm ≥85%: 0-90°*** 75 lm/w ≤5700K 65 50,000 hrs 5 years
10) Wall-wash Luminaires 575 lm ≥60%: 0-90°** 45 lm/w ≤5000K 80 50,000 hrs 5 years

11) Track or Mono-point Directional Lighting Fixtures

250 lm

>85%: 0–90º

45 lm/W

<5000K

80

50,000 hrs

5 years
12) Vertical Refrigerated Case Lighting

Center-mounted*:

100 lm/ft

End-mounted**:

50 lm/ft

 

Vertical Lighting

>95%: 10º-90º

50 lm/W <5000K 80 50,000 hrs 5 years
13) Horizontal Refrigerated Case Lighting

 

100 lm/ft

Horizontal Lighting

>95%: 0º-90º

50 lm/w

<5000K

80

50,000 hrs 5 years
14) Display Case Lighting

End-mounted**:

50 lm/ft

≥95%: 0º-80º 50 lm/W < 5000K 80 35,000 hrs 5 years

15) 2x2 Luminaires for Ambient Lighting
of Interior Commercial Spaces

2,000 lm

Spacing Criteria:

0º-180º:

1.0-1.20

90º-270º:

1.0-2.0

≥75%: 0-60°

85 lm/W <5000K 80 50,000 hrs 5 years
16) 1x4 Luminaires for Ambient Lighting
of Interior Commercial Spaces
1,500 lm

Spacing Criteria:

0º-180º:

1.0-2.0

90º-270º:

1.0-2.0

≥75%: 0-60°

85 lm/W <5000K 80 50,000 hrs 5 years
17) 2x4 Luminaires for Ambient Lighting
of Interior Commercial Spaces
3,000 lm

Spacing Criteria:

0º-180º:

1.0-2.0

90º-270º:

1.0-2.0

≥75%: 0-60°

85 lm/W <5000K 80 50,000 hrs 5 years
18) High-bay Fixtures for Commercial and Industrial Buildings 10,000 lm >30%: 20-50º 80 lm/W < 5700K 70 35,000 hrs 5 years
19) Low-bay Fixtures for Commercial and Industrial Buildings 5,000 lm ≥30% 20-50° 80 lm/w ≤5700K 70 35,000 hrs 5 years
20) High-bay Aisle Lighting 10,000 lm >50%: 20º-50º
>30%: 0º-20º
80 lm/W <5700K 70 35,000 hrs 5 years
Retrofit Kits and Replacement Lamps***
21) Retrofit Kits for Outdoor Pole/Arm-mounted
Area and Roadway
Luminaires
1,000 lm =100%: 0–90º, <10%: 80–90º 70 lm/W <5700K 65 50,000 hrs 5 years
22) Retrofit Kits for Outdoor Pole/Arm-mounted
Decorative Luminaires
1,000 lm >65%: 0–90º 60 lm/W <5700K 65 50,000 hrs 5 years
23) Retrofit Kits for Large Outdoor
Pole/Arm-mounted Area and
Roadway Luminaires
1,000 lm

=100%: 0-90°

<10%:80-90°

70 lm/w ≤5700K 65 50,000 hrs 5 years
24) Retrofit Kits for Outdoor Wall-mounted Area Luminaires 300 lm

=100%: 0-90°

<10%: 80-90°

70 lm/w ≤5700K 65 50,000 hrs 5 years
25) Retrofit Kits for Parking Garage Luminaires 2,000 lm

≥30%: 60-80°

<25%: 70-80°

75 lm/w ≤5700K 65 50,000 hrs 5 years
26) Retrofit Kits for Fuel Pump Canopy Luminaires 2,000 lm

≥40%: 0-40°

≥40%: 40-70°

80 lm/w ≤5700K 65 50,000 hrs 5 years
27) Retrofit Kits for 2x2 Luminaires for
Ambient Lighting of Interior
Commercial Spaces
2,000 lm

Spacing Criteria:

0-180°:

1.0-20.

90-270°:

1.0-2.0

≥75%: 0-60°

85 lm/w ≤5000K 80 50,000 hrs 5 years
28) Retrofit Kits for 1x4 Luminaires for
Ambient Lighting of Interior
Commercial Spaces
1,500 lm

Spacing Criteria:

0-180°:

1.0-20.

90-270°:

1.0-2.0

≥75%: 0-60°

85 lm/w ≤5000K 80 50,000 hrs 5 years
29) Retrofit Kits for 2x4 Luminaires for
Ambient Lighting of Interior
Commercial Spaces
3,000 lm

Spacing Criteria:

0-180°:

1.0-20.

90-270°:

1.0-2.0

≥75%: 0-60°

85 lm/w ≤5000K 80 50,000 hrs 5 years
30) Retrofit Kits for High-bay Fixtures for Commercial and Industrial Building 10,000 lm ≥30%: 20-50° 80 lm/w ≤5700K 70 35,000 hrs 5 years
31) Retrofit Kits for Low-bay Fixtures for Commercial and Industrial Building 5,000 lm ≥30%: 20-50° 80 lm/w ≤5700K 70 35,000 hrs 5 years
32) Four-foot Linear Replacement Lamps

2 Lamps, Tested in Fixture:

3,000 lm

 

Bare Lamp:

1,600 lm

Spacing Criteria:
0-180º: 1.0-2.0
90-270º: 1.0-2.0
≥75%: 0-60°

In Fixture:
85 lm/W


Bare Lamp:
100 lm/W

<5000K 80 50,000 hrs 5 years
To view the requirements for DLC under v1.5, click here. To view the requirements for DLC under v1.6, click here. To view the requirements for DLC under v1.7, click here.

*     Bilateral, symmetric light distribution on two hemispheres

**    One-sided, single hemisphere light distribution

***   Bilateral for surface-mounted units, single hemisphere for corner-mounted units

****  Retrofit Kits and Replacement Lamps must be tested inside fixtures, per the policies for those products. See Retrofit Kit Policy and Four-Foot Linear Replacement Lamp Policy for details.

 

Power Factor and Total Harmonic Distortion: In addition to the specific requirements above, all DLC-qualified luminaires must have a power factor of ≥0.9, and a current THD of ≤20%. This applies to every category listed in Table 2.0. Qualified products must meet the requirements in their worst case loading conditions.

 

Tolerances: Below are tolerances that are applicable to all categories listed above in Table v2.0. These tolerances are referenced in the ENERGY STAR Manufacturer’s Guide. For zonal lumen tolerances specific to each category, please refer to Table 5.

 

Table 2.0a: Tolerances

Performance Metric Tolerance
Light Output
-10%
Luminaire Efficacy
-3%
Allowable CCT
Defined by ANSI C78.377
CRI
-2 points
Power Factor
-3%
Total Harmonic Distortion
+5%

 

 

 

Lumen Maintenance: DLC has two options for demonstrating lumen maintenance compliance. Option 1 is using component-level performance through the TM-21 protocols, which leverage the LM-80 performance and In-Situ Temperature of the LED device. More information is available in the Application Instructions. For products where the required lifetime is longer than the projection method allows, the necessary lumen maintenance minimums at the end of the allowable projection period are as follows. These percentages result from solving an exponential decay function for 35,000 and 50,000 hours. Please note that content and applicability of LM-80 reports will follow the guidance issued by ENERGY STAR.

 

Table 2: Option 1 TM-21 Projected Lumen Maintenance Requirements

Projected End Point Required Lumen Maintenance for 35,000 Hour Products Required Lumen Maintenance for 50,000 Hour Products
33,000
≥71.44%
>79.03%
36,000
L70 ≥ 35,000
>77.35%
38,500
L70 ≥ 35,000
>75.98%
42,000
L70 ≥ 35,000
>74.11%
44,000
L70 ≥ 35,000
>73.06%
48,000
L70 ≥ 35,000
>71.01%
49,500
L70 ≥ 35,000
>70.25%
50,000
L70 ≥ 35,000
>70.00%

 

Option 2 is to conduct 6000-hours of luminaire-level testing. For Option 2, DLC uses a pass/fail threshold for lumen maintenance compliance as established in the ENERGY STAR Manufacturer’s Guide v2, pg. 7. The requirements differ for applications requiring 35,000 hours of useful life and those requiring 50,000 hours, as follows:

 

Table 3: Option 2 Lumen Maintenance Requirements

Lumen Maintenance to L70

Required Lumen Maintenance at 6,000 Hours

35,000 hours

94.1%

50,000 hours

95.8%

These percentages result from solving an exponential decay function for 35,000 and 50,000 hours, respectively, to determine the minimum lumen maintenance necessary to achieve those thresholds. Products can demonstrate compliance with testing longer than 6,000 hours, according to the table below:

 

Table 4: Exponential Decay Function L=e-αt

Hours of Testing L70 = 35,000 hrs L70=50,000 hrs
6,000
94.1%
95.8%
7,000
93.1%
95.1%
8,000
92.2%
94.5%
9,000
91.2%
93.8%
10,000
90.3%
93.1%
11,000
89.4%
92.5%
12,000
88.5%
91.8%
13,000
87.6%
91.1%
14,000
86.7%
90.5%
15,000
85.8%
89.9%

 

When applying the lumen maintenance in accordance with these protocols, DLC applies a tolerance of 5% to drive currents tested under LM-80.

 

Zonal Lumen Distribution: The following tolerances apply to the zonal lumen distribution requirements:

Table 5: Zonal Lumen Tolerances

Category

Zone (degrees)

Nominal Requirement (%)

Tolerance (%)

Actual Requirement (%)

1

0-90

100

-1

≥99

80-90

<10

+3

<13

2

0-90

>65

-3

>62

3

0-90

100

-3

≥97

80-90

<10

+3

≤13

4
90-110
<15
+3
≤18
>110
0
+3
≤3
5
60-80
>30
-3
≥27
70-80
≤25
+3
≤28

6

0-40

≥40

-3

≥37

40-70

≥40

-3

≥37

7
0-90
>85
-3
>82
0-90
>85
-3
>82
8
0-90
≥85
-3
≥82
9
0-90
≥85***
-3
≥82
10
0-90
≥60**
-3
≥57

11

0-90

>85

-3

>82

12- center

10-90

>95

-3

>92

12-end

10-90

>95

-5

>90

13
0-90
>95
-3
>92

14

0-80

>95

-5

>90

15

SC:0-180

1.0-2.0

+0.1

0.9-2.1

SC: 90-270
1.0-2.0
+0.1
0.9-2.1
ZL: 0-60°
≥75
-3
≥72
16

SC:0-180

1.0-2.0

+0.1

0.9-2.1

SC: 90-270
1.0-2.0
+0.1
0.9-2.1
ZL: 0-60°
≥75
-3
≥72
17

SC:0-180

1.0-2.0

+0.1

0.9-2.1

SC: 90-270
1.0-2.0
+0.1
0.9-2.1
ZL: 0-60°
≥75
-3
≥72

18

20-50

>30

-10

≥20

19

20-50

>30

-10

≥20

20

20-50

>50

-10

≥40

0-20

>30

-10

≥20

21

0-90

100

-1

≥99

80-90

≤10

3

≤13

22

0-90

>65

-3

>62

23
0-90
100
-1
≥99
80-90
≤10
+3
≤13
24
0-90
100
-3
≥97
80-90
≤10
+3
≤13
25
60-80
≥30
-3
≥27
70-80
≤25
+3
≤28
26
0-40
≥40
-3
≥37
40-70
≥40
-3
≥37
27
0-180
1.15-1.3
±0.1
1.05-1.40
90-270
1.2-1.6
±0.1
1.1-1.7
28

SC:0-180

1.0-2.0

+0.1

0.9-2.1

SC: 90-270
1.0-2.0
+0.1
0.9-2.1
ZL: 0-60°
≥75
-3
≥72
29

SC:0-180

1.0-2.0

+0.1

0.9-2.1

SC: 90-270
1.0-2.0
+0.1
0.9-2.1
ZL: 0-60°
≥75
-3
≥72
30
20-50
≥30
-10
≥20
31
20-50
≥30
-10
≥20
32

SC:0-180

1.0-2.0

+0.1

0.9-2.1

SC: 90-270
1.0-2.0
+0.1
0.9-2.1
ZL: 0-60°
≥75
-3
≥72

 

Flood and Spot Lighting Categories:

For both architectural and landscape/accent flood and spot lighting categories, manufacturers must declare the NEMA Beam Classification (see chart below) of their luminaire in the 0-180 degree and 90-270 degree planes. DLC will verify these claims against the IES files provided.

Table 6: NEMA Beam Classification

NEMA Beam Classification
Beam Spread Range
1
10-18°
2
18-29°
3
29-46°
4
46-70°
5
70-100°
6
100-130°
7
≥130°

 

Wall-wash Luminaires:

For clarity, the zonal lumen criteria for this category is that ≥60% of the lumens must be produced in the “forward” hemisphere, towards the wall.

 

Stairwell and Passageway Lighting:

DLC requires that products in the Stairwell and Passageway Lighting category to include integral controls for occupancy sensing and bi-level dimming. Documentation must be provided to demonstrate bi-level dimming capabilities, and occupancy sensing options must be designated clearly in the model number. Manufacturers must also declare whether the unit is intended to be surface-mounted or corner-mounted. All performance requirements in Technical Requirements Table v2.0 refer to the full power operating mode.

 

DLC Retrofit Kit Policy

DLC will accept QPL applications for SSL Retrofit Kits for certain available categories. The testing and reporting requirements described in the link below are intended to subject the retrofit kits to real-world thermal conditions in order to assure confidence in lumen maintenance. For more information, please refer to http://www.designlights.org/solidstate.manufacturer.instructions.outdoorretrofit.php.

 

DLC Four-foot Linear Replacement Lamp Policy

DLC will accept QPL applications for 4’ linear tube-style products intended to replace fluorescent lamps in this category. The testing and reporting requirements described in the link below are intended to evaluate the performance both of the lamp itself, and its performance in reference 2x4 troffers, their most common application. For more information, please refer to http://www.designlights.org/solidstate.manufacturer.instructions.linearreplacementlamps.php. Note that this category covers all four-foot LED tubes, including those that are direct, simple replacements for fluorescent tubes and those that require modifications to the existing fixture (such as bypassing the
existing ballast).

 

 

Disclaimer: DesignLights Consortium® Qualified Products List holds the right to make revisions or changes to current specifications at any given period.  Manufacturers will be given advance notice when these changes occur.

 

Please proceed to the next page